Parameter Description
 Maximum Capacity  2000 W
AC Input Data
Parameter Description
 Input Voltage (Nominal)  110 VAC / 220 VAC
 Operating Voltage  85-290 VAC
 Max. Input Current  13 A
 Input Frequency  45 Hz – 65 Hz
 Power Factor  ≥ 0.99 (220VAC @30% to 100% load)
DC Output Data
Parameter Description
 Output Voltage Range  42 to 58 VDC (Rated 53.5V)
 Max Output Current  41.7 A
 Peak Efficiency  >96 %
 THD  ≤ 5% @50% to 100% Load
Dimension
Parameter Description
 Dimension (H x W x D)  41.5 x 106.4 x 291 mm
Control and Monitor
Parameter Description
 Communication Protocol  CAN
 LED  Green-normal, yellow-alarm, red-fault
Certification and Safety
Parameter Description
 Certifications  CE CUL CB UL 62368-1, EN 62368-1, IEC 62368-1
 Electromagnetic Compability  EN 55032 class B, EN 55035, IEC 61000-3-2, IEC 61000-3-3

Performance Curve

Product Data Sheet and User Manual

Download Product Data Sheet

Download Products User Manual